Uninterruptible power supplies for server racks and network cabinets, sized to the load and the runtime you need. Sourced to order; send the equipment list and the team will quote a suitable UPS.
An uninterruptible power supply sits between the mains and your equipment and keeps power flowing from its battery when the mains fails or dips. For a server it does two things: it rides through the short interruptions that would otherwise reboot the machine, and in a longer outage it gives the server minutes to shut down cleanly before the battery runs out. Most models can signal the server to start that shutdown automatically.
This page explains the choices. UPS systems are sourced to order, sized to the equipment they will protect and the runtime you need, for server rooms, comms rooms and network cabinets across Qatar.
| Type | How it works | Typical use |
|---|---|---|
| Standby (offline) | Passes mains through and switches to battery when it fails | Desktops, a single small switch |
| Line-interactive | Corrects under- and over-voltage without using the battery; switches to battery on failure | Network cabinets, small servers, branch offices |
| Online double-conversion | Runs the load from the inverter at all times, so output is clean regardless of the mains | Production servers, storage, anything sensitive to supply quality |
Online units cost more and use a little more electricity, but the equipment never sees a transfer and is isolated from the dips, spikes and frequency changes that occur on a busy supply.
Send the requirement by WhatsApp on +974 5521 2108, email sales@serverdove.com or use the contact page. List the equipment to be protected, the runtime you want and the cabinet it will go in, and the team will propose a unit and quote it with the PDUs to distribute its output. UPS systems can be installed and connected as part of a rack build with a cabinet and server power supplies.
Add up the actual power draw of everything it will protect, in watts, and choose a UPS whose watt rating is comfortably above that, with the load at no more than about 80 percent. Then pick the runtime: a few minutes is enough for an automatic shutdown, while riding out an outage needs a bigger battery. Send the equipment list and the team will do the sums.
VA is apparent power and watts is real power; the watt rating is lower and is the one that matters for the load. A 1500 VA unit might be rated 1000 or 1350 W depending on the model, so compare the watt figures when choosing.
Line-interactive units are cheaper and suit network cabinets, small servers and branch offices. Online units run the load from the inverter at all times, so the equipment never sees a transfer or a mains disturbance; choose online for production servers and storage.
It depends on the load and the battery. At full rated load most rack units give only a few minutes, which is designed for a clean shutdown rather than continued operation. Lighter loads run longer, and external battery packs extend runtime where it is needed.
Yes. Connected by USB or serial, or through a network management card, the UPS tells the operating system or the virtualisation host that it is on battery, and the shutdown runs on a schedule you set. The network card is the better option where the UPS feeds more than one machine.
Sealed lead-acid batteries typically need replacing every three to five years, sooner in a hot room, and the UPS will warn when they weaken. Lithium models last longer at a higher price. ServerDove can quote replacement batteries for a unit it supplied.
DDR5 doubles bandwidth and capacity per module and is the only option on every current platform. DDR4 is...
Most outages were visible weeks before they happened. A degraded RAID battery, a drive logging errors since spring,...
Spinning drives still run most backup targets, file servers, and NAS builds, and the market is full of...
RAID levels appear in nearly every storage decision, usually as though everyone already knows why RAID 6 beats...